Deye SUN-50K-G04 — 50 kW Three-Phase On-Grid Inverter, 4 MPPT, 98.7% Peak Efficiency

⚡ Quick answer

What is the SUN-50K-G04?

  • AC output: 50 kW rated, 55 kVA max apparent power, three-phase 220/380V or 230/400V, 3L/N/PE
  • PV input: up to 65 kW across 4 MPPT trackers in a 3+3+3+3 string layout, 200–1,000 V MPPT window, 1,100 V max PV voltage
  • Efficiency: 98.7% peak, 98.1% Euro, MPPT tracking above 99%
  • PV current: 40+40+40+40 A maximum operating input current, comfortable headroom for current-dense modern panels
  • Build: IP65, only 39 kg, 434×570×243 mm, permissible altitude 4,000 m, 5-year warranty

The Deye SUN-50K-G04 is a 50 kW three-phase grid-tied inverter for projects with one clear objective: cut the daytime electricity bill as hard as possible, without batteries and without backup circuits. Its real advantages are 98.7% peak and 98.1% Euro efficiency — higher than a hybrid of the same size — and a 39 kg body that makes installation on a factory or commercial roof dramatically simpler. It is one of the units our engineers specify for businesses whose consumption peaks during daylight hours. If you are still sizing the project, start with the calculator and look at the equipment we build systems around.

What is the Deye SUN-50K-G04, and how does it differ from a hybrid?

The SUN-50K-G04 is a three-phase string inverter with a single job: convert DC from the array into AC that offsets what the building would otherwise buy from PEA. There is no battery circuit, and when the grid goes down the inverter stops exporting as grid-connection safety standards require. Removing the charging and transfer circuitry that a hybrid must carry buys two measurable advantages. First, efficiency: 98.7% peak and 98.1% Euro, higher than a hybrid of comparable capacity. Second, mass: 39 kg in a 434×570×243 mm cabinet, which cuts lifting effort and removes most wall-structure constraints. On the DC side, four MPPT trackers take three strings each (3+3+3+3) with a 200–1,000 V tracking window and 1,100 V maximum PV input — a range that permits long strings, reducing home-run cabling and balance-of-system cost on large roofs. Maximum operating PV current of 40+40+40+40 A leaves room for current-dense modern modules without shortening strings to dodge a current ceiling. The unit also supports zero export for sites that must not feed power back to the grid. For a wider view of our work, see services and the solar cost in Phuket page.

Highlights from the datasheet

  • 98.7% peak and 98.1% Euro efficiency: the Euro figure reflects real all-day operation and matters far more to annual yield than a brief peak reading.
  • Four MPPTs, 3+3+3+3 strings: twelve strings on a single inverter, ideal for factory and commercial roofs split across several areas, with shaded groups isolated from the rest.
  • 200–1,000 V MPPT window, 1,100 V max PV: long strings are practical, which means fewer home runs and less balance-of-system cost on large arrays.
  • 65 kW of PV on a 50 kW inverter: deliberate oversizing keeps production strong through early mornings, late afternoons and overcast monsoon days.
  • 40+40+40+40 A maximum PV current: current-dense modern panels fit without trimming string length purely to stay under a current limit.
  • Only 39 kg: in a 434×570×243 mm cabinet, far easier to lift and mount than a hybrid of the same capacity — less installation time and less site risk.
  • IP65 with zero export support: suitable for outdoor mounting and configurable to prevent any reverse feed where site conditions require it.

Key specifications (SUN-50K-G04)

Specification Datasheet value
Rated AC Output Active Power50 kW
Max. AC Output Apparent Power55 kVA
Max. AC Output Current83.3 / 79.7 A
Rated Output Voltage / Grid Connection Form3 เฟส 220/380V, 230/400V (0.85Un–1.1Un), 3L/N/PE
No. of MPP Trackers / No. of Strings per MPPT4 ชุด / 3+3+3+3 สตริง
MPPT Voltage Range200–1,000 V
Max. PV Input Voltage1,100 V
Max. PV Input Power65 kW
Max. Operating PV Input Current40+40+40+40 A
Max. Efficiency98.7%
Euro Efficiency98.1% (MPPT >99%)
Ingress Protection (IP) RatingIP65
Operating Temperature Range-25 ถึง +60°C (ลดกำลังเมื่อเกิน 45°C)
Permissible Altitude4,000 ม.
Weight / Cabinet Size (W×H×D)39 กก. / 434×570×243 มม. (ไม่รวมคอนเนกเตอร์และขายึด)
Warranty5 ปี

Note: every figure above comes straight from the Ningbo Deye Inverter Technology Co., Ltd. datasheet. Actual system design (strings per MPPT, cable sizing, breakers) must be calculated for each site.

Why this model suits Phuket

  • Businesses that consume during daylight: hotels, offices, retail and factories in Phuket peak exactly when the sun does, so a grid-tied system offsets consumption immediately without battery investment.
  • Heat and derating: the datasheet gives an operating range of -25 to +60°C with derating above 45°C, so a shaded, ventilated mounting position measurably affects year-round output.
  • Coastal conditions: the IP65 rating supports outdoor installation, but on seafront sites we still position equipment away from direct salt spray.
  • PEA connection conditions: sites that must not export to the grid can use the zero export function, a common requirement on commercial connections in Thailand.

Who it suits

  • Factories and warehouses: wide roofs, daytime operation, and a straightforward goal of maximum bill reduction per baht invested.
  • Hotels and resorts on daytime load: properties not yet ready to invest in storage but wanting to start reducing energy cost now.
  • Offices and retail: air-conditioning and lighting that follow business hours line up almost perfectly with the solar production curve.
  • Sites with an existing standby generator: buildings that already have backup power do not need to buy that capability twice through the inverter.
  • Owners planning phased expansion: grid-tied systems scale by adding inverters and arrays in later phases without disturbing the original installation.

Summary

The Deye SUN-50K-G04 is the straightforward choice when the goal is purely daytime bill reduction: 50 kW output, 65 kW of PV across four MPPTs, 98.7% peak efficiency, and a 39 kg body that installs faster and more safely than a comparable hybrid. Pearl Solar Energy's engineers and technicians handle design, installation and PEA permits from start to finish. Review our services, or contact us with twelve months of electricity bills and we will model the array size that pays back fastest on your site.

See other models from this brand on the Deye overview, or browse all the equipment we install.

Download the datasheet (PDF) — full manufacturer specification sheet

Frequently asked questions

What are the key specifications of the Deye SUN-50K-G04?

It is a three-phase string inverter rated at 50 kW active output with 55 kVA maximum apparent power and maximum AC output currents of 83.3 A and 79.7 A. Grid connection is three-phase 220/380V or 230/400V in a 3L/N/PE configuration. The DC side has four MPPT trackers in a 3+3+3+3 string layout, a 200–1,000 V tracking window, 1,100 V maximum PV input voltage, and 40+40+40+40 A maximum operating PV current, accepting up to 65 kW of panels. Efficiency is 98.7% peak and 98.1% Euro. The unit is IP65 rated, permitted to 4,000 m altitude, weighs 39 kg, measures 434×570×243 mm and carries a 5-year warranty.

How much PV can the SUN-50K-G04 handle, and how are strings laid out?

Maximum PV input power is 65 kW on a 50 kW inverter, so oversizing the array is standard practice and keeps production healthy in early morning, late afternoon and under monsoon cloud. Strings are distributed across four MPPT trackers taking three strings each — twelve strings in total — within a 200–1,000 V operating window, with open-circuit voltage never exceeding 1,100 V on the coldest morning of the year. Each tracker accepts up to 40 A of operating current, which is ample headroom for the current-dense panels now common on commercial projects.

Does this model provide backup power during an outage?

No. The SUN-50K-G04 is a pure grid-tied inverter with no battery circuit, and when the utility supply fails it stops producing, as grid-connection safety standards require, so that no power is fed back onto lines where crews may be working. If your site also needs backup, a hybrid inverter with a battery circuit is the appropriate choice, or you can rely on an existing standby generator of the kind most hotels and factories already have installed. We can assess which approach makes better financial sense for your particular load profile.

What warranty does the SUN-50K-G04 carry?

The manufacturer datasheet states a 5-year warranty for this grid-tied family, which is shorter than the term quoted for the brand's hybrid models. Before finalising the specification we recommend requesting the Thailand warranty terms in writing from the distributor, including claim procedures, spare-part lead times and who covers labour for a replacement. On a commercial project the real cost of a fault is measured in days of lost production, not in the price of the hardware, so local support response is the term worth negotiating hardest.

Should I choose the SUN-50K-G04 or a 50 kW hybrid?

It comes down to one question: does an outage cost your business money? If not, or if you already run a standby generator, this grid-tied model is the better value — 98.7% peak efficiency beats a comparable hybrid, 39 kg makes installation far simpler, and there is no battery investment. If you run cold rooms, servers or occupied guest rooms that cannot go dark, a hybrid with a battery circuit is worth the extra cost and complexity. Either way we handle the PEA connection application and verify the chosen model's certification documents with the distributor before filing.